FBHL Crossflow Cooling Tower
The FBHL crossflow cooling tower provided by WANXIANG is reliable cooling equipment designed with a combined multi-module structure. The single module cooling tower is dissected into smaller upper box and lower box, bringing convenience to transportation and filed disassembly and avoiding the long occupation of the construction site. Therefore, this low noise cooling tower, to a great degree, could help promote the management and working efficiency of a production site.
Moreover, of an excellent noise controlling design, this crossflow cooling equipment is highly suitable for working occasions where noise should be strictly controlled, such as the hotel, shopping center, and office building. It is also applicable in the working condition where the temperature difference is 4-8°C. Given this, this commercial cooling tower is used as the cooling equipment for central air-conditioning system.
Applications
1. Temperature of liquids to be cooled: 30-40℃
2. Maximum temperature difference: 15℃, Optimum temperature difference: 4-7℃
3. Suitable wet bulb temperature for projects: ≥10℃
4. Average noise value: dB55-69
5. Suitable cooling rate for projects: more than 22L/s
6. Cooling capacity of single module: 312KW-1,063KW
7. The crossflow cooling tower is suitable for use in quiet places, such as laboratories, data centers, the air conditioners for civil use and so on.
Working Principle of FBHL Crossflow Cooling Tower
The heat of flowing fluid inside the coils will be transferred to the spay water which, being heated, becomes saturated vapor. The heat will be exhausted by the draught fan and the water will be recollected by the catch basin and then be cycled again. Especially, the circulating water will flows in the same direction as that of the fresh wind and be cooled down via PVC radiation fin in the process of circulation.
Features of FBHL Crossflow Cooling Tower
1. Low noise. This environment-friendly cooling tower is credited for its low noise and mixed flow design. As its coils are arranged at both sides, the heat rejection device enjoys a larger space for air flow. And the fan throat, of a maximized size, could significantly expand the airflow area. The wide fan blades which, of lower rotating speed, are often used in the aviation and could effectively reduce wind pressure and lower the noise.
2. No deposits. Temperature of the spray water of this crossflow cooling machinery is controlled under the temperature that facilitates the scale formation. Moreover, the pipe is thoroughly damped, making it hard for the deposit to come into being;
3. Easy maintenance. This crossflow closed circuit cooling tower enjoys a large internal space which brings convenience to you during inspection and maintenance. Entering the tower through the access door, operator or inspector could go to check such key components as the coils and spray system directly.
4. Belt driven fan
Flow 98.6-89.6°F (GPM) | Fan | Spew Pump | Inlet(out) (In) | Shipping Weight (lbs) | Operating Weight (lbs) | Dimensions | Basic Dimensions | ||||||||
Power (HP) | Airflow (CFM) | Power (HP) | Flow (GPM) | L (mm) | W (mm) | H (mm) | h1 (mm) | h2 (mm) | A (mm) | B (mm) | |||||
84 | 3 | 19059 | 1×1 | 105 | 2" | 2376 | 4070 | 1528 | 1896 | 3550 | / | / | 1780 | 2150 | |
99 | 3 | 19059 | 1×1 | 105 | 2" | 2530 | 4136 | 1528 | 1896 | 3550 | / | / | 1780 | 2150 | |
125 | 4 | 36000 | 1.5×1 | 198 | 3" | 3410 | 5940 | 1850 | 2250 | 3550 | / | / | 2100 | 2500 | |
136 | 5.5 | 40235 | 1.5×1 | 198 | 3" | 3630 | 6160 | 1850 | 2250 | 3550 | / | / | 2100 | 2500 | |
165 | 5.5 | 40235 | 2×1 | 264 | 4" | 4620 | 7590 | 1850 | 2896 | 3550 | / | / | 2100 | 3150 | |
183 | 7.5 | 44471 | 3×1 | 303 | 4" | 4840 | 7755 | 1850 | 2896 | 3550 | / | / | 2100 | 3150 | |
238 | 7.5 | 59294 | 1.5×2 | 396 | 4"(2) | 6600 | 11660 | 2250 | 3792 | 3550 | / | / | 2500 | 4050 | |
256 | 7.5 | 59294 | 1.5×2 | 396 | 4"(2) | 7062 | 12100 | 2250 | 3792 | 3550 | / | / | 2500 | 4050 | |
297 | 10 | 64588 | 2×2 | 514 | 4"(2) | 9174 | 16170 | 2476 | 4792 | 3550 | / | / | 2750 | 5050 | |
341 | 10 | 64588 | 2×2 | 514 | 4"(2) | 9790 | 16830 | 2476 | 4792 | 3850 | 1921 | 1929 | 2750 | 5050 | |
403 | 15 | 76235 | 2×2 | 514 | 5"(2) | 11770 | 18700 | 2476 | 4792 | 3850 | 1921 | 1929 | 2750 | 5050 | |
443 | 15 | 76235 | 2×2 | 514 | 5"(2) | 14960 | 24200 | 2476 | 4792 | 4150 | 2067 | 2083 | 2750 | 5050 | |
451 | 15 | 91059 | 3×2 | 620 | 5"(2) | 15400 | 24640 | 2690 | 4792 | 3850 | 1921 | 1929 | 2940 | 5050 | |
495 | 15 | 91059 | 3×2 | 620 | 5"(2) | 16500 | 25300 | 2690 | 4792 | 4150 | 2067 | 2083 | 2940 | 5050 | |
531 | 20 | 114353 | 3×2 | 738 | 5"(2) | 17050 | 27060 | 2976 | 5220 | 3850 | 1921 | 1929 | 3250 | 5470 | |
560 | 20 | 114353 | 3×2 | 738 | 5"(2) | 18260 | 27940 | 2976 | 5220 | 4150 | 2067 | 2083 | 3250 | 5470 | |
634 | 25 | 137647 | 4×2 | 884 | 5"(2) | 20460 | 32340 | 3620 | 5220 | 4150 | 2067 | 2083 | 3870 | 5470 | |
663 | 25 | 137647 | 4×2 | 884 | 5"(2) | 21890 | 33440 | 3620 | 5220 | 4150 | 2067 | 2083 | 3870 | 5470 | |
1. Model Code: FBHL-363T(GS) 2. Reference conditions 3. This crossflow cooling apparatus is applicable to civil air-conditioning projects where noise control is strictly required and the temperature difference is 4 to 8 °C . 4. This closed circuit cooling tower has been certified to the CTI (Center Testing International) certificates. It is a combined closed circuit cooling equipment which is constructed by some of the above single cell cooling towers whose technical specifications are applicable to the equipment. 5. Data in the above table are based on those of the cooling tower whose surface air cooler is made of hot-dip galvanized steel. 6. For more available quality apparatuses, please resort to the WXSWL13.6 software which will offer you best selection suggestions. |
Multi-module Combined Cooling Tower
As the following table shows, two cooling towers of this type could form a double-module cooling equipment arranged back to back. The technical parameters of such multi-module cooling tower could be deducted by the following analogy.
Model | Flow 98.6- 89.6°F (GPM) | Fan | Spew Pump | Inlet(out) (In) | Shipping Weight (lbs) | Operating Weight (lbs) | Dimensions | Basic Dimensions | |||||||
Power (HP) | Airflow (CFM) | Power (HP) | Flow (GPM) | L (mm) | W (mm) | H (mm) | h1 (mm) | h2 (mm) | A (mm) | B (mm) | |||||
Specifications of the above types cooling tower are omitted here | |||||||||||||||
1330 | 15×3 | 228706 | 2×6 | 1543 | 5"(6) | 25344 | 45540 | 2476×3 | 4792 | 4150 | 2067 | 2083 | 2750×3 | 5050 | |
1978 | 15×3 | 364235 | 3×8 | 2479 | 5"(8) | 40040 | 63360 | 2690×4 | 4792 | 4150 | 2067 | 2083 | 2940×4 | 5050 | |
2802 | 20×3 | 571765 | 3×10 | 3692 | 5"(10) | 64350 | 107800 | 2976×5 | 5220 | 4150 | 2067 | 2083 | 3250×5 | 5470 | |
Specifications of other types cooling tower are omitted here |