Spiral Degassing and Decontamination Device
Request a Quote
Water treatment device for gas water separation, sedimentation, and filtration
Applications
Ideal for air conditioning cooling water systems and industrial circulating water systems, ensuring clean and efficient operation.
Features
- Significantly reduces system commissioning time after the first water injection, eliminating the need for additional air release valves
- Allows for contaminant removal while the system is in operation
Use Conditions
| System Water Quality | pH>6.5, Totla Hardness < 700mg/1(CaC03), Totla Hardness Total Alkalinity< 800(CaC03) |
| Water Temperature | < 90℃ (temperature of water passing water treatment system) |
| Water Pressure | < 1.0Mpa (custom requirements < 2.5Mpa ) |
| Concentration Rate | < 3.5 (for cooling water system) |
| Working Temperature | -40℃~55℃ |
| Humidity | < 90% (below 20℃) |
Model Options
| Model | Connection | Total Height (mm) | Body Diameter (mm) | External Diameter of Flange (mm) | Distance from Top to Inlet/Outlet (mm) | Total Width (mm) | Weight (kg) |
| DN 50 | 565 | 175 | 165 | 365 | 350 | 14.5 | |
| DN 65 | 565 | 175 | 185 | 365 | 350 | 14.5 | |
| DN 80 | 765 | 270 | 200 | 450 | 470 | 31.0 | |
| DN 100 | 765 | 270 | 220 | 450 | 470 | 33.5 | |
| DN 125 | 980 | 360 | 250 | 550 | 635 | 59.0 | |
| DN 150 | 980 | 360 | 285 | 550 | 635 | 63.0 | |
| DN 200 | 1193 | 450 | 340 | 708 | 774 | 115 | |
| DN 250 | 1577 | 600 | 406 | 892 | 990 | 215 | |
| DN 300 | 1742 | 600 | 460 | 1032 | 1006 | 255 | |
| DN 350 | 1986 | 800 | 580 | 1109 | 1214 | 490 | |
| DN 400 | 2159 | 800 | 508 | 1252 | 1220 | 545 | |
| DN 500 | 2590 | 1000 | 715 | 1470 | 1580 | 882 | |
| DN 600 | 3085 | 1200 | 840 | 1756 | 1870 | 1750 |