DTSD342-9 Electric Power Distribution Monitor
General introduction:
DTSD342-9 electric power distribution monitor integrates measurement and recording, electric energy metering, teleindication and telecontrol, large screen LCD display and network communication, which can measure voltage, current, power, power factor, frequency and other parameters of the grid. Besides, the monitor possesses the function of 2~50 times harmonic analysis, calculation of a number of electric energy quality parameters as well as measurement of active and reactive electric energy. RS-485 communication interface is configured which supports MODBUS-RTU and DL/T645 dual communication protocol. With switch input and output function, analog transmission output can be configured.
The monitor can be widely used in substation automation, industrial control and industrial automation system, energy management system, residential power monitoring and other occasions.
It complies with the following standards:
1. GB/T17215.301-2007 special requirements of multi-function electric energy meter.
2. GB/T17215.322-2008 static active electric energy meter (class 0.2S and class 0.5S).
3. GB/T17215.323-2008 static reactive electric energy meter (class 2 and class 3).
4. DL/T 614-2007 multifunctional electric energy meter.
5. DL/T 645-2007 communication protocol of multifunctional electric energy meter.
6. Modbus-RTU.
- Three-phase four-wire(without PT) connection diagram
- Three-phase four-wire(with PT) connection diagram
- Three-phase three-wire connection diagram
Items | Technical index | |
Wiring form | three-phase three-wire, three-phase four-wire, single phase | |
Measurement | Voltage | Reference voltage Un:AC380V, AC220V, AC100V, AC57.7V Measurement range:10V~1.3Un Power consumption:< 0.05VA(single phase) Accuracy: RMS 0.2 % Resolution: 0.01V |
Current | Rated current In:0.3A, 1A, 1.5A, 5A Measurement range:0.001In~10A Power consumption:< 0.05VA(single line rated current) Accuracy: RMS 0.2 % Resolution: 0.001A | |
Power (active / reactive/ apparent) | Accuracy: 0.2% Resolution: 0.001kW/kVar/kVA | |
Grid frequency | Measurement range:45Hz~65Hz Accuracy: 0.2% Resolution: 0.01Hz | |
Metering | Active electric energy | Metering accuracy class: 0.5S Resolution: 0.01kWh |
Reactive electric energy | Metering accuracy class: class 2 Resolution: 0.01kvarh | |
digital signal | electric energy pulse output | 2 channel electric energy(active and reactive) pulse output optocoupler isolation, 4000VRMS |
Switch output (optional) | 2 channel electromagnetic relay output normally open Contact rating: AC 250V /3A; DC 30V /3A | |
Switch input (optional) | 4 channel dry contact input optocoupler isolation, 4000VRMS | |
analog signal | Transmission (analog) output (optional) | 4 channel analog signal output current output type (4~20Ma or 0~20Ma or 0~24mA) voltage output type (0~5Vor 0~10V) accuracy: 0.5% |
Communication | RS-485 communication port (optional) | Interface type: two-line half duplex communication rate: 600bps~38400bps Protocol: Modbus-RTU and DL/T-645 |
Environment | Working temperature | -25℃~+60℃ |
Limit working temperature | -35℃~+70℃ | |
Relative humidity | ≤95%(RH) | |
Others | Power supply | AC or DC power supply maximum input range: 40V~420V Power consumption: ≤1W, 2VA |
size | Outline size(mm):96×96×95 Hole size(mm):92×92 | |
Weight | About 450g |
Main functions
DTSD342-9 series products contain a total of 13 models. For specific information, please refer to the following product model and function check table.
Model/Function | 9V | 9A | 9B | 9H | 9G | 9P | 9Q | 9C | 9M | 9W | 9E | 9N | 9X |
Voltage measurement | √ | √ | √ | √ | √ | ||||||||
Current measurement | √ | √ | √ | √ | √ | ||||||||
Frequency measurement | √ | √ | √ | √ | |||||||||
Active power measurement | √ | √ | √ | √ | √ | ||||||||
Reactive power measurement | √ | √ | √ | √ | √ | ||||||||
Power factor measurement | √ | √ | √ | √ | √ | ||||||||
Apparent power measurement | √ | √ | √ | √ | |||||||||
Active electric energy measurement | √ | √ | √ | √ | |||||||||
Reactive electric energy measurement | √ | √ | √ | ||||||||||
Active electricity pulse output port | √ | √ | √ | √ | |||||||||
Reactive electricity pulse output port | √ | √ | √ | ||||||||||
Off-limit alarm | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | √ | ||
Harmonic measurement and analysis | √ | ||||||||||||
Transmission output | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ | ||
Switch input(teleindication) | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ |
Switch output (telecontrol) | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ |
RS-485communicaiton | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ | △ |
Note: "√" indicates that the function is possessed, and "△" indicates the function is optional.
Main features
1. Our product adopts high-precision sampling and measuring unit together with high-speed MCU data processing unit, which can realize high precision, wide range and accurate measurement as well as fast data analysis.
2. Wide viewing angle LCD display is used to show richer contents.
3. LCD display is equipped with white backlight to meet the requirement of consulting data in dark environment.
4. nonvolatile memory is adopted to store all kinds of data, which can save data for a long time without losing data due to power failure.
5. Support RS-485 communication port and industrial standard communication protocol, convenient and flexible for network construction.
Different communication modules are availabe to satisfy different interface requirements of various users.
WILLFAR as a reliable electric power distribution monitor manufacturer, mainly manufacture meter data management instrument, like electrical power data logger, data concentrator, data collector, and power monitor for smart meter system. To serve daily life much better, WILLFAR company also provides custom meter data management and electrical energy efficiency management solutions in customer needs.