Coal Fired Utility Boiler

Coal Fired Utility Boiler
Request a Quote

Rated steam output: 10-75t/h
Rated working pressure: 1.6-5.3Mpa
Rated steam temperature: 204-485℃
Fuel type: anthracite coal, meagre coal, lignitous coal, bituminous coal

The coal-fired utility boiler is used specifically in power plants and features a natural circulation with Π type structure. Due to limitations in volume and transportation, we will ship the boiler, unassembled, to the customer for assembly on site. If needed, we will send a technicians to provide on-site installation and debugging services.

Technical parameters:
Type Rated steam output ( t/h ) Rated working pressure ( MPa ) Rated steam temperature ( ℃ ) Water supply temperature( ℃ )
Heated area Design emission temperature (℃)
Furnace ( m2 ) Superheater ( m2 ) Convention tube( m2 ) Economizer ( m2 ) Air pre-heater ( m2 )
CFU10 10 1.6 204 104 57.5 - 230.3 188.8 138.4 163
2.5 226 57.5 - 230.3 188.8 138.4 168
2.5 400 57.5 82.7 230.3 188.8 138.4 169
CFU20 20 1.6 204 104 97 - 215.7 157.1 410 158
2.5 226 97 - 215.7 157.1 410 163
2.5 400 97 133.4 215.7 157.1 410 160
CFU35 35 1.6 204 104 131.7 - 376 288 640 160
2.5 226 131.7 - 376 288 640 165
2.5 400 131.7 176.5 376 288 640 162
3.82 450 192.6 290.6 - 629 640 160
CFU65 65 3.82 450 104 582 582 - 1052 1145 161
CFU75 75 5.3 485 150 554 554 - 1060 1699 159
Features

1. The burner uses travelling grate bar and water walls are arranged around the furnace. An economizer and air pre-heater are installed at the flue tail.
2. The boiler features a large capacity, and here at Xineng, we manufacture boilers with capacities of 75tons/hour or more.
3. Based on different coal types, the furnace volume should be properly adjusted to facilitate coal combustion, and ensure the boiler has sufficient thermal efficiency.
4. No coking in the furnace.
5. When designed with an exhaust gas temperature of about 160℃ , the heating efficiency is high.

Related products
Send Message
Other Products
Inquiry
Inquiry