HD912 Heat Detector

HD912 Heat Detector
Request a Quote

HD912 Heat Detector

Our HD912 heat detector meets the requirements of UL521 and EN 54-5. Our product provides fast and reliable response for heat over 57°C (135°F) or rate-of-rise detection. The heat detector includes 2-wire and 4-wire models, while it is subject to panel compatibility limits and compliance with corresponding NFPA 72E standards, local codes, and ordinances.

Besides, with advanced detection and discrimination algorithms, our heat detector features an easy installation and maintenance. The durable sensor head makes you to worry no more for replacement. Meanwhile the SMD circuit board is designed to satisfy quality and reliability. Our product provides N/C (normal/close)-N/O (normal/open) selectable relay output, while Auto Reset function is also offered for security systems. We also provide a five-year limited warranty to our products.

Models

HD912-2

2 wire heat alarm

HD912-2L

2 wire heat alarm with remote LED output

HD912-4

4 wire heat alarm (12/24VDC)

HD912-4B

4 wire heat alarm with buzzer (12/24VDC)

HD912-4AR

4 wire heat alarm with auto-reset function (12/24VDC)

HD912-4ARB

4 wire heat alarm with auto-reset function and buzzer (12/24VDC)

Technical Specifications

Model

2/4 Wire

Voltage DC(Min./Max.)

Standby Current (Max.)

Alarm Current (12/24V)

Surge Current (Max.)

Start-Up Time (Max.)

Max. Current

Cycle Time

Alarm contact

Certifi ed

Base Model No.

HD912-2

2

10~33V

45µA

50mA

100µA

30 Seconds

80mA

1-3 Seconds

UL/EN

P/N852001

HD912-2L

2

10~33V

45µA

50mA

100µA

30 Seconds

80mA

1-3 Seconds

UL/EN

P/N854001

HD912-4-12/24

4

12/24V

45µA

30mA

100µA

30 Seconds

1- 3Seconds

Form A

UL/EN

P/N854001

HD912-4AR-12/24

4

12/24V

45µA

30mA

100µA

30 Seconds

1-3 Seconds

Form A Auto Reset

CE

P/N854001

HD912-4ARB-12/24

4

12/24V

45µA

30mA

100µA

30 Seconds

1-3 Seconds

Form A Auto Reset

CE

P/N854001

HD912-4B-12/24

4

12/24V

45µA

30mA

100µA

30 Seconds

1- 3Seconds

Form A

CE

P/N854001

Detailed Information

Response Temperature

135°F(57°C) or 15°F(9.3°C)/min Rate-of-Rise

Monitoring Spacing

40 feet * 40 feet

Reset Voltage

Less than 1 volt

Alarm Indicator

LED continuously emitting red light

Remote Output

25 mA max., diode gate

Temperature Range

-10°Cto 50°C

Max. Current

80mA maximum

Humidity

0 to 95% RH, no condensation or icing

Alarm Contact

(for 4-wire) NO or NC Operation, Form A 1.0A@30VDC/0.5A@125VAC

Dimension

100mm(dia.) x 46mm (ht) with base

Weight

120g/set with base


 