Ceiling Filter Media
- FRS-560
- FRS-600
Model: FRS-560G/FRS-600G
Type: filter media pad or filter media roll;
Filtration Materials: quality polyester fiber with graduated density;
Filter classification standard EN779: F5;
EUROVENT4/5 classification: EU5;
Filtration accuracy: ≥1μm (for main particles to be filtered);
DIN53438 Non-flammability standard: F1;
Average arrestance: 95%(ASHRAE52.1-1992);
Final resistance: (suggested)100Pa-(Maximum)200Pa;
Dust holding capacity: 450g/m2;
Maximum Working temperature: 100℃;
Transient temperature: 120℃.
Features of Ceiling Filter Media
1.The roof filter media are designed for the primary filtration or pre-filtration of common ventilation systems where there's heavy pollution;
2. We use processes of combing and layering to make the filter with quality polyester fiber of graduated densities and to coat it with mesh or cloth at its air inlet side;
3. As this filter media have a large capacity to hold dust, they are more durable and can be used several times after being cleaned, so they are more cost-effective;
4. This air filter media complies with the GB5455-85B1 National Fire Protection classification standard as well as the UL 900 Class 2 flammability rating (US);
5. This air filtration product could be combined with paper or metal frames and therefore made into the panel filters or pleat filters.
Applications of Ceiling Filter Media
1. The ceiling filter media filters particles of 1-10μm out of the air current or serves as a pre-filter in air filtration systems while equalizing the flow.
2. This type of filtration media has been widely used in air conditioning and ventilation systems of industrial, civil and commercial areas where such processes as spraying and coating, electrical plating, surface treatment, and other construction projects pollute the air.
3. The ceiling filter media is also used in the HVAC industry, household appliance industry, motorcycle industry, electronics industry, pharmaceutical industry, food industry, and packaging materials production.
Technical Parameters of Ceiling Filter Media
Model | ||
Thickness | 22mm | 22mm |
Air flow speed(Testing) | 0.25 m/s | 0.25 m/s |
Rated air flow | 900 m3/h | 900m3/h |
Average arrestance (EN779) | 95% | 95% |
Initial resistance(Pa) | 25 | 25 |
Final resistance(Pa) | 450 | 450 |
Dust holding capacity | 450g/m2 | 550g/m2 |
Filter classification | F5 | F6 |
Standard dimensions | 1.6 x 14m, 1.6 x21m, 2 x21m, 2x20m |
* Customized ceiling filter media are also available.