Industrial Cable Manufacturer
- Optical unit aluminum clad steel wire
- Optical unit anticorrosive oil aluminum clad steel wire aluminum wire
OPGW fiber integrates ground electrode and photo-communication functions all in cable one unit. This product is mainly applied to 35kV, 110kV, 220kV, 500kV, 750kV telecommunication lines of high voltage transmission systems built on stilts. OPGW fiber is also suitable for replacing old ground wires of high voltage transmission system built on stilts to add to existing optical communication lines, conduct short circuit current and protect the system from lightning strikes.
SPFO will carefully design the structure of the optical cable according to the specific service environment (like distance between towers, requirement of sag, ice load, wind load, allowed tensile force at the suspension point, message capacity, short circuit current and so on). Users can specify the structure as well.
Parameter Technical parameterItem | Content | Typical value |
Quantity of optical fiber | 2~48 | |
Protecting tube | Material | stainless steel tube |
Outer diameter/mm | 1.5~6 | |
Stranded single wire | Material | Aluminum clad steel, aluminum, aluminum rod |
Diameter/mm | 1.5~6 | |
Maximum outer diameter | mm | 18 |
Maximum tensile force | kN | 280 |
Maximum sectional area | mm² | 200 |
Maximum short circuit current | 400-200℃(Ka²*S) | 100 |
Range of operating temperature | ℃ | -40~+65 |
Compressive resistance | N/100mm | 2200 |
* The structure of optical cable and quantity of core can be custom-made according to customer requirements. |
G.652.D | G.655 | 50/125μm | 62.5/125μm | ||
Attenuation | @850nm | - | - | ≤3.0dB/km | ≤3.0dB/km |
@1300nm | - | - | ≤1.0dB/km | ≤1.0dB/km | |
@1310nm | ≤0.36dB/km | ≤0.36dB/km | - | - | |
@1550nm | ≤0.22dB/km | ≤0.23dB/km | - | - | |
Bandwidth | @850nm | - | - | ≥500MHz·km | ≥200MHz·km |
@1300nm | - | - | ≥1000MHz·km | ≥600MHz·km | |
Fiber cutoff wavelength | ≤1260nm | ≤1260nm | - | - | |
Polarization mode dispersion | Single optical fiber | ≤0.20ps/√km | ≤0.20ps/√km | - | - |
Link value (M=20, Q=0.01%) | ≤0.10ps/√km | ≤0.10ps/√km | - | - |
Item | Inspection standard | procedure of inspection | Requirements |
tension | IEC 60794-4-10 | According to the change of optical cable's structure | Additional attenuation≤0.05dB |
pressure | IEC 60794-20-9.4.5 | 2200N/100mm, 10min, 3 times interval 1m | Additional attenuation≤0.1dB, non-mechanical damage |
Backward and forward bending | IEC 60794-4-20-9.4.3 | R=15~20*D | Additional attenuation≤0.05dB, non-mechanical damage |
Seepage test | IEC 60794-4-10-9.8 | Length of sample: 0.5m, 20±5℃, height of the water: 1m, 1h | Non-seepage |
Dripping test | IEC 60794-4 | Length of sample: 0.3m, 70±1℃, 24h | The filler and composition won't outflow or drip out. |
Temperature recycle test | IEC 60794-4-20-9.6 | -40℃~+70℃ | Additional attenuation≤0.1dB |
- Smaller diameter; the additional load to the tower is lower.
- The design of the stainless steel tube and stranded core is excellent. Optical fiber extra length is accurate.
- The stainless steel tube has a higher tensile strength, and will protect the optical fiber.
- The optical unit locates the center of the stainless steel tube to get the advantages of distortion resistance and side-pressure resistance.
- The good security ensures that the fiber cannot be cut by knife or stolen. The damage resistance of this product is excellent.
- There are various combinations in the armored layer or electrical properties and mechanical properties.
DL/T 832-2003 Optical Fiber Composite Ground Wire
IEC 60794-4-10-2014 Aerial Optical Wire used in Power Line
Aerial