Service Entrance Cable

Service Entrance Cable
Request a Quote

Service entrance cable consists of AA-8000 series aluminum alloy conductors, insulated with sunlight resistant type XHHW-2 cross-linked polyethylene (XLPE) and wrapped together with a neutral conductor using a reinforced tape. It has a sunlight resistant PVC jacket that is available in various colors.

We offer two types of SE cables: SER cable has 2-4 stranded phase conductors and bare ground wire; SEU cable has two parallel phase conductors surrounded by a concentric bare ground wire.

Aluminum SE cable is to be used at 600V and at a max. conductor temperature of 90℃ for outdoor uses in wet, damp or dry locations.

Applications:

Aluminum SE cable is intended for electric power transmission from the junction box to the meter box and from the meter base to the distribution cabinet. It is also suitable for other applications as specified in the NEC.

Standards:

Our SE cable meets UL 44 and UL 854. It has passed the following tests: current overload test, tensile testing, horizontal flame test, 720h sunlight resistance test, aging test on insulation materials, dielectric voltage withstand test, etc.

Specifications:
The structure size of SER cable
Conductor Size Nominal Cond. Diameter Insulation Thickness Nominal Diameter Approx. Weight Allowable Ampacities
(AWG or kcmil) Inch mm mils mm mils mm Kg/Km LBS/1000FT 60℃ 75℃ 90℃
Three Conductor With Bare Ground
8-8-8-8 0.134 3.4 45 1.14 14.2 14.2 208 140 35 40 45
6-6-6-6 0.169 4.29 45 1.14 16.3 16.3 282 190 40 50 55
4-4-4-4 0.213 5.41 45 1.14 19.1 19.1 395 265 55 65 75
4-4-4-6 0.213 5.41 45 1.14 18.4 18.4 370 249 55 65 75
2-2-2-2 0.268 6.81 45 1.14 22.6 22.6 570 383 75 90 100
2-2-2-4 0.268 6.81 45 1.14 21.7 21.7 530 356 75 90 100
1-1-1-1 0.299 7.59 55 1.4 25.5 25.5 723 486 85 100 115
1-1-1-3 0.299 7.59 55 1.4 24.5 24.5 673 452 85 100 115
1/0-1/0-1/0-1/0 0.336 8.53 55 1.4 27.9 27.9 876 589 100 120 135
1/0-1/0-1/0-2 0.336 8.53 55 1.4 26.8 26.8 813 546 100 120 135
2/0-2/0-2/0-2/0 0.376 9.55 55 1.4 30.4 30.4 1063 714 115 135 150
2/0-2/0-2/0-1 0.376 9.55 55 1.4 29.2 29.2 984 661 115 135 150
3/0-3/0-3/0-3/0 0.423 10.74 55 1.4 33.4 33.4 1298 872 130 155 175
3/0-3/0-3/0-1/0 0.423 10.74 55 1.4 32 32 1200 806 130 155 175
4/0-4/0-4/0-4/0 0.475 12.07 55 1.4 36.8 36.8 1589 1068 150 180 205
4/0-4/0-4/0-2/0 0.475 12.07 55 1.4 35.2 35.2 1466 985 150 180 205
250-250-250-250 0.52 13.21 65 1.65 40.6 40.6 1902 1278 170 205 230
250-250-250-3/0 0.52 13.21 65 1.65 39 39 1771 1190 170 205 230
The structure size of SER cable
Conductor Size Nominal Cond. Diameter Insulation Thickness Nominal Diameter Approx. Weight Allowable Ampacities
(AWG or kcmil) Inch mm mils mm mils mm Kg/Km LBS/1000FT 60℃ 75℃ 90℃
Four Conductor With Bare Ground
8-8-8-8-8 0.134 3.4 45 1.14 404 15.9 257 173 35 40 45
6-6-6-6-6 0.169 4.29 45 1.14 466 18.3 350 235 40 50 55
4-4-4-4-4 0.213 5.41 45 1.14 544 21.4 494 332 55 65 75
4-4-4-4-6 0.213 5.41 45 1.14 528 20.8 468 315 55 65 75
2-2-2-2-2 0.268 6.81 45 1.14 644 25.4 714 480 75 90 100
2-2-2-2-4 0.268 6.81 45 1.14 624 24.6 675 453 75 90 100
1-1-1-1-1 0.299 7.59 55 1.4 729 28.7 909 611 85 100 115
1-1-1-1-3 0.299 7.59 55 1.4 707 27.8 859 577 85 100 115
1/0-1/0-1/0-1/0-1/0 0.336 8.53 55 1.4 796 31.4 1100 739 100 120 135
1/0-1/0-1/0-1/0-2 0.336 8.53 55 1.4 772 30.4 1037 697 100 120 135
2/0-2/0-2/0-2/0-2/0 0.376 9.55 55 1.4 869 34.2 1334 896 115 135 150
2/0-2/0-2/0-2/0-1 0.376 9.55 55 1.4 841 33.1 1256 844 115 135 150
3/0-3/0-3/0-3/0-3/0 0.423 10.74 55 1.4 954 37.6 1628 1094 130 155 175
3/0-3/0-3/0-3/0-1/0 0.423 10.74 55 1.4 922 36.3 1530 1028 130 155 175
4/0-4/0-4/0-4/0-4/0 0.475 12.07 55 1.4 1049 41.3 1993 1339 150 180 205
4/0-4/0-4/0-4/0-2/0 0.475 12.07 55 1.4 1013 39.9 1870 1257 150 180 205
250-250-250-250-250 0.52 13.21 65 1.65 1159 45.6 2388 1605 170 205 230
250-250-250-250-3/0 0.52 13.21 65 1.65 1123 44.2 2258 1517 170 205 230
The structure size of SEU cable
Conductor Size Nominal Cond. Diameter Insulation Thickness Nominal Diameter Approx. Weight Allowable Ampacities
(AWG or kcmil) Inch mm mils mm mils mm Kg/Km LBS/1000FT 60℃ 75℃ 90℃
Two Conductor With Bare Concentric Ground
2008/8/8 0.134 3.4 45 1.14 398×254 15.7×10.0 165 111 35
40
2006/6/6 0.169 4.29 45 1.14 443×277 17.5×10.9 219 147 40
50
2004/4/4 0.213 5.41 45 1.14 504×308 19.8×12.1 304 204 55
65
2004/4/6 0.213 5.41 45 1.14 501×305 19.7×12.0 280 188 55
65
2002/2/2 0.268 6.81 45 1.14 598×367 23.6×14.5 439 295 75
90
2002/2/4 0.268 6.81 45 1.14 578×347 22.7×13.7 399 268 75
90
2001/1/1 0.299 7.59 55 1.4 680×416 26.8×16.4 554 372 85
100
2001/1/3 0.299 7.59 55 1.4 654×390 25.8×15.4 504 339 85
100
1/0-1/0-1/0 0.336 8.53 55 1.4 730×442 28.7×17.4 669 450 100
120
1/0-1/0-2 0.336 8.53 55 1.4 717×429 28.2×16.9 610 410 100
120
2/0-2/0-2/0 0.376 9.55 55 1.4 796×482 31.3×19.0 811 545 115
135
2/0-2/0-1 0.376 9.55 55 1.4 784×470 30.9×18.5 736 494 115
135
3/0-3/0-3/0 0.423 10.74 55 1.4 856×512 33.7×20.1 984 661 130
155
3/0-3/0-1/0 0.423 10.74 55 1.4 847×503 33.3×19.8 894 601 130
155
4/0-4/0-4/0 0.475 12.07 55 1.4 926×548 36.5×21.6 1198 805 150
180
4/0-4/0-2/0 0.475 12.07 55 1.4 929×551 36.6×21.7 1091 733 150
180