Hybrid Inverter

Hybrid Inverter
Request a Quote

A single-phase/three-phase photovoltaic (PV) energy storage system is also known as a hybrid system. Our hybrid inverter is designed to optimize the utilization of solar power, store excess energy for later use, and enable off-grid operation if needed.

Features
  • Integrated on- and off-grid solution
  • Compact design
  • LCD touch screen
  • Seamless switch between on-grid and off-grid modes
  • Diesel generator remote control
  • Programmable mode of operation
Technical Parameters
 
HPS5000TLS
HPS7500TLS
HPS10000TLS
AC (On-grid)
Apparent power 6.25kVA 9.4kVA 12.5kVA
Rated power 5kW 7.5kW 10kW
Rated voltage 230V 230V 230V
Rated current 21.5A 32.6A 43.4A
Voltage range 210V-250V 210V- 250V 210V-250V
Rated frequency 50/60Hz 50/60Hz 50/60Hz
Frequency range 47~51.5/57~61.5Hz 47~51.5/57~61.5Hz 47~51.5/57~61.5Hz
THDI < 3% < 3% < 3%
Power factor 0.8leading~0.8lagging 0.8leading~0.8lagging 0.8leading~0.8lagging
AC connection L/N/PE L/N/PE L/N/PE
AC (Off-grid)
Apparent power 6.25kVA 9.4kVA 12.5kVA
Rated power 5kW 7.5kW 10kW
Rated voltage 230v 230v 230V
Rated current 21.5A 32.6A 43.4A
THDU ≤2% linear ≤2% linear ≤2% linear
Rated frequency 50/60Hz 50/60Hz 50/60Hz
Overload capacity 110%-10mins 120%-1min 110%-10mins 120%-1min 110%-10mins 120%-1min
DC (Battery and PV)
Max. PV open-circuit voltage 600V 750V 750V
Recommended PV power 6kWp 9kWp 12kWp
PV MPPT voltage rang 125V-550V 370V-600V 370V-600V
Number of MPPT 2 2 2
Recommended rated battery voltage 300V 350V 450V
Battery voltage range 85-600V 280-700V 280-700V
Full load battery voltage range 250-600V 300-700V 400-700V
Max. charge/discharge power 5kW 7.5kW 10kW
Max. charge/discharge current 25A 25A 25A
Basic Parameters
Protection devices PV DC switch, battery breaker and fuse, PV fuse, AC input breaker, load breaker
Protection degree IP65 IP65 IP65
Noise < 65dB(A)@1m < 65dB(A)@1m < 65dB(A)@1m
Operating temperature -25°C~ 55°C -25°C~ 55°C -25°C~ 55°C
Cooling Forced air Forced air Forced air
Relative humidity 0~95% no condensation 0~95% no condensation 0~95% no condensation
Max. altitude 6000m (derate over 3000m) 6000m (derate over 3000m) 6000m (derate over 3000m)
Dimensions (W×H×D) 600×700×250mm 600×700×250mm 600×700×250mm
Weight 50kg 50kg 50kg
Topology Transformerless Transformerless Transformerless
Lighting protection Type II Type II Type II
Transfer between on/off grid Automatic≤10ms Automatic≤10ms Automatic≤10ms
Standby consumption < 20W < 20W < 20W
Communication
Display Touch screen Touch screen Touch screen
Communication interface RS485/CAN RS485/CAN RS485/CAN
 
HPS7500TL
HPS10000TL
AC (On-grid)
Apparent power 9.4VA 12.5kVA
Rated power 75kW 10kW
Rated voltage 400V 400V
Rated current 10.8A 14.4A
Voltage range 360V- 440V 360V- 440V
Rated frequency 50/60Hz 50/60Hz
Frequency range 47~51.5/57~61.5Hz 47~51.5/57~61.5Hz
THDI < 3% < 3%
Power factor 0.8leading - 0.8lagging 0.8leading - 0.8lagging
AC connection 3/N/PE 3/N/PE
AC (Off-grid)
Apparent power 9.4kVA 12.5kVA
Rated power 7.5kW 10kW
Rated voltage 400V 400V
Rated current 10.8A 14.4A
THDU ≤2% linear ≤2% linear
Rated frequency 50/60Hz 50/60Hz
Overload capacity 110%-10mins 120%-1min 110%-10mins 120%-1min
DC (Battery and PV)
Max. PV open-circuit voltage 750V 750V
Recommended PV power 9kWp 12kWp
PV MPPT voltage rang 370V-600V 370V-600V
Number of MPPT 2 2
Recommended rated battery voltage 350V 450V
Battery voltage range 280-700V 280-700V
Full load battery voltage range 300-700V 400-700V
Max. charge/discharge power 7.5kW 10kW
Max. charge/discharge current 25A 25A
Basic Parameters
Protection devices PV DC switch, battery breaker and fuse, PV fuse, AC input breaker, load breaker
Protection degree IP65 IP65
Noise < 65dB(A)@1m < 65dB(A)@1m
Operating temperature -25°C~ 55°C -25°C~ 55°C
Cooling Forced air Forced air
Relative humidity 0~95% no condensation 0~95% no condensation
Max. altitude 6000m (derate over 3000m) 6000m (derate over 3000m)
Dimensions (W×H×D) 600/700/250mm 600/700/250mm
Weight 50kg 50kg
Topology Transformerless Transformerless
Lighting protection Type II Type II
Transfer between on/off grid Automatic≤10ms Automatic≤10ms
Standby consumption < 20W < 20W
Communication
Display Touch screen Touch screen
Communication interface RS485/CAN RS485/CAN
 
HPS30
HPS50
HPS100
HPS120
HPS150
AC (On-grid)
Apparent power 33kVA 55kVA 110kVA 132kVA 165kVA
Rated power 30kW 50kW 100kW 120kW 15OkW
Rated voltage 400V 400V 400V 400V 400V
Rated current 43A 72A 144A 173A 217A
Voltage range 360V-440V 360V-440V 360V-440V 360V- 440V 360V-440V
Rated frequency 50/60Hz 50/60Hz 5060Hz 50/60Hz 50/60Hz
Frequency range 45-55/55-65Hz 45-55/55-65Hz 45-5555-65HHz 45-55155-65Hz 45-55/55-65Hz
THDI < 3% < 3% < 3% < 3% < 3%
Power factor 0.8leading~0.8lagging 0.8leading~0.8lagging 0.8leading~0.8lagging 0.8leading~0.8lagging 0.8leading~0.8lagging
AC connection 3/N/PE 3/N/PE 3/N/PE 3/N/PE 3/N/PE
AC input 60kVA 100kVA 200kVA 240kVA 240kVA
AC (Off-grid)
Apparent power 33kVA 55kVA 110kVA 132kVA 165kVA
Rated power 30kW 50kW 100kW 120kW 150kW
Rated voltage 400V 400V 400V 400V 400V
Rated current 43A 72A 144A 173A 217A
THDU ≤2% linear ≤2% linear ≤2% linear ≤2% linear ≤2% linear
Rated frequency 50/60Hz 50/60Hz 5Q60Hz 50/60Hz 50/60Hz
Overload capacity 110%-10mins 120%-1min 110%-10mins 120%-1min 110%-10mins 120%-1min 110%-10mins 120%-1min 110%-10mins 120%-1min
DC (Battery and PV)
Max. PV open-circuit voltage 1000V DC 1000V DC 1000V DC 1000V DC 1000V DC
Max. PV power 45kWp 75kWp 150kWp 18OkWp 225kWp
PV MPPT voltage rang 480V-800V DC 480V-800V DC 480V-800 DC 480V-800V DC 480V-800V DC
Battery voltage range at maximum charge power 450V-600V 500V-600V 500V-600V 517V-600V 500V-600V
Battery voltage range 352-600V 352-600V 352-600V 352-600V 352-600V
Max. charge power 45kW 75kW 150kW 180kW 225kW
Max. discharge power 33kW 55kW 110kW 132kW 165kW
Max. charge current 100A 150A 300A 350A 450A
Max. discharge current 93A 156A 3134 374A 467A
Basic Parameters
Protection degree IP20 IP20 IP20 IP20 IP20
Noise < 65dB(A)@1m < 65dB(A)@1m < 65dB(A)@1m < 65dB(A)@1m < 65dB(A)@1m
Operating temperature -25.C- 55.C -25°C~ 55°c -25.C— 55°c -25C- 55.c -25°C- 55c
Cooling Forced air Forced air Forced air Forced air Forced air
Relative humidity 0-95% no condensation 0-95% no condensation 0-95% no condensation 0-95% no condensation 0-95% no condensation
Max. altitude 6000m (derate over 3000m) 6000m (derate over 3000m) 6000m (derate over 3000m) 6000m (derate over 3000m) 6000m (derate over 3000m)
Dimensions (W×H×D) 700×1660×600omm 950×1860×750mm 1200×1900×800mm 1200×1900×80omm 1200×1900×800mm
Weight 355kg 610kg 948kg 1025kg 1230kg
Build-in transformer Yes Yes Yes Yes Yes
Transfer between on/off grid Automatic≤10ms Automatic≤10ms Automatic≤10ms Automatic≤10ms Automatic≤10ms
Standby consumption < 30w < 30W < 30w 30W 30W
Communication          
Display Touch screen Touch screen Touch screen Touch screen Touch screen
Communication interface RS485/CAN RS485/CAN RS485/CAN RS485/CAN RS485/CAN
Related products
Send Message
Other Products
Inquiry
Inquiry