DTSD342-HLQ Rack Mount Multi Circuit Power Monitor
General introduction:
DTSD342-HLQ rack mount multi circuit power monitor integrates measuring and recording, large screen LCD display, 485 communication into one electrical power monitor, mainly used in the monitoring of electrical parameters in multi distribution circuits.
Items | Technical index | |
Power distribution system | Low voltage three-phase distribution circuit, low voltage single-phase distribution circuit | |
Measuring parameters | Bus voltage, outgoing current, active power, reactive power, apparent power, frequency, power factor, electric energy | |
Bus voltage | Rated input | 220V AC |
Measurement range | 40~400V AC | |
Overload | Instantaneous voltage 2 times /10 seconds | |
Current circuit | Load circuit | Three-phase 4 circuits or single-phase 12 circuits (12 circuit current) |
Rated input | Primary winding: 50A, 100A, 200A | |
Overload | Lasts 1.2 times, instantaneous current 10 times /5 seconds | |
Matching current transformer | close-loop transformer(class 1) or open-loop transformer(class 1) | |
Measurement accuracy | Current, voltage: class 0.5 | |
Metering accuracy | Active electric energy: class 1 resolution: 0.01kWh reactive electric energy: class 2 resolution: 0.01kvarh | |
Input frequency | 45Hz~65Hz | |
Power supply | AC/DC40V~420V | |
Power consumption | ≤5VA | |
Digital communication | Interface type: standard 1 channel two-line half duplex RS485 interface communication rate:1200~38400bps protocol: support MODBUS-RTU and DL/T645-2007 | |
Display | LCD display | |
Clock | < 0.5 second per day | |
Working environment | Working temperature:-25℃~+60℃ limit working temperature:-35℃~+70℃ Relative humidity:≤93%(RH) Altitude≤2500m | |
Installation mode | Flush mount or 35mm standard rail mount | |
Outline size | 96×96×62.8mm(flush mount); 72×101.7×63mm(rail mount) | |
Weight | About 450g |
Main features
1. DTSD342-HLQ flush mount multi circuit power monitor has the advantages of high precision, good stability, strong practicability, powerful function, small size, easy installation, and excellent EMC performance.
2. Different communication modules are optional to meet different interface requirement of various customers.
3. Configured one channel RS-485 communication interface, our monitor supports MODBUS-RTU and DL/T645-2007 dual communication protocol.
4. Large screen LCD display, data cycle display.
5. Freezing and event recording
Main functions
The monitor can measure and display circuit bus voltage, current of four distribution three-phase circuits, active power, reactive power, apparent power, power factor and frequency. Through RS485 communication interface, our monitor can exchange data with the upper computer and calculate positive and negative active electric energy and reactive four-quadrant electric energy. Meanwhile, our monitor equips RS485 communication interface supporting DL/T 645-2007 and MODBUS RTU dual communication protocol, which greatly facilitates the automatic management of electricity utilization, as well as the wiring, installation, commissioning of the system. Besides, the user's investment and system costs are therefore reduced.
WILLFAR as a leading rack mount multi circuit power monitor manufacturer, mainly manufacture meter data management and energy efficiency management instrument. To serve daily life much better, WILLFAR company also provides custom electrical energy management solutions as well as smart metering system in customer needs.