OPGW Cable
Overhead power ground wires, or OPGW cables, are used in 500KV, 220KV and 110KV lines with a pressure over 110KV and for longer distances, usually over 250m. The outer OPGW is made of metal armor which resists electro-corrosion. These aerial power cables work well with short circuit currents and metal armor conductors to reduce tension strength.
Features
1. Extruded Aluminium Core Tube: resistant to bending and kinks, core tube can safely be routed to closures without armour, easy access to optical core
2. Corrosion Resistance: meets IEEE construction guidelines for use in high corrosion sites
3. Superior Electrical Performance: aluminium core tube increases conductor cross-section and improves short-circuit capacity
4. Excellent Lightning Resistance: fewer aluminum alloy wires are needed and in some cases can be completely replaced wtih ACS wires.
5. High Performing Cables: all fibers are housed in core tubes available in a wide range of inside diameters
Central Optical Fiber SUS Tube Structure (Parts) | |||
Structure Drawing | Structure: central optical fiber SUS tube structure with single stranded layer | ||
Order Type Model | OPGW-1C1/36 (M48/R60-12) | OPGW-1C1/40 (M58/R72-16) | |
Max. fiber count | 36 | 40 | |
Tube size | φ3.2 mm | φ3.5mm | |
Cable diameter | φ9.6 mm | φ10.5 mm | |
Cross-section carry area | 48 mm2 | 58 mm2 | |
Cable weight | 338 kg/km | 400 kg/km | |
Rated Tensile Strength(RTS) | 59 kN | 71 kN | |
DC resistance at 20℃ | 1.782 Ω/km | 1.490 Ω/km | |
Short current capacity (40~200℃) | 11 kA2·s | 16 kA2·s | |
Linear expansion coefficient | 13.0×10-6/℃ | 13.0×10-6/℃ | |
Young’s modulus | 162.0 kN/mm2 | 162.0 kN/mm2 |
Structure Drawing | Structure: central optical fiber SUS tube structure with double stranded layers | ||
Order Type Model | OPGW-2C1/30 (M127/R78-137) | OPGW-2C1/40 (M163/R100-226) | |
Max. fiber count | 30 | 40 | |
Tube size | φ3.0 mm | φ3.4 mm | |
Cable diameter | φ15.0 mm | φ17.0 mm | |
Cross-section carry area | 127 mm2 | 163 mm2 | |
Cable weight | 529 kg/km | 673 kg/km | |
Rated Tensile Strength(RTS) | 77 kN | 99 kN | |
DC resistance at 20℃ | 0.329 Ω/km | 0.255 Ω/km | |
Short current capacity (40~200℃) | 137 kA2·s | 226 kA2·s | |
Linear expansion coefficient | 17.5×10-6/℃ | 17.5×10-6/℃ | |
Young’s modulus | 97.3 kN/mm2 | 97.3 kN/mm2 |