Air Cooler (Used for Cold Room)

Air Cooler <small>(Used for Cold Room)</small>
Air Cooler <small>(Used for Cold Room)</small>
Air Cooler <small>(Used for Cold Room)</small>
Air Cooler <small>(Used for Cold Room)</small>
Air Cooler <small>(Used for Cold Room)</small>
Air Cooler <small>(Used for Cold Room)</small>
Air Cooler <small>(Used for Cold Room)</small>
Request a Quote

Yanghu Refrigeration supplies air coolers specially used for cold rooms. Our air cooler takes up little space with its compact and lightweight structure. With its efficient and uniform storage temperature, the air cooler achieves quick cooling and greatly improves the freshness of stored food.

Our D-Series evaporative air coolers are produced based on our years of experience in designing and manufacturing cold rooms. Each of the DD-model, DL-model and DJ-model work for cold rooms needing different storage temperatures.

Model Selections

The DD-model air cooler is used in cold rooms with a storage temperature at about -18°C. The cold room stores meat, fish and other frozen food.

Technical Parameters of the DD-Model Air Cooler
Model *Nominal Cooling Capacity
W(Kcal/h) t (storage temperature) =-18℃
△ t= t (storage temperature)-t0=7℃
Cooling Area
(m2)
Fan Distance
(mm)
Cooling Equipment Defrost Heater Weight
(kg)
Note Voltage
(V)
Quantity Diameter
(D mm)
Air Volume
(m3 /h)
Air Pressure
(Pa mmH2O)
Shot Range
(m)
Motor Power
(W)
Motor voltage
(V)
Fan Coil Power
(kW)
Water Coil power
(kW)
DD-1.5/8 1,400(1,200) 8 6 1 ¢300 1,700 98(10) 8 120 380 0.9 0.6 220 27 Applicable to
R134a
R404A
and
R507
DD-2.35/12 2,350(2,000) 12 6 2 ¢300 2×1,700 98(10) 8 2×120 380 1.8 0.9 220 40
DD-3.0/15 3,000(2,600) 15 6 2 ¢300 2×1,700 98(10) 8 2×120 380 1.8 0.9 220 46
DD-4.0/22 5,000(3,450) 21.5 6 3 ¢300 3×1,700 98(10) 8 3×120 380 1.8 0.9 220 55
DD-6.0/30 6,000(5,150) 30 6 2 ¢400 2×3,000 118(12) 12 2×250 380 2.6 1.3 220 70
DD-8.0/40 8,000(6,900) 40 6 2 ¢400 2×3,000 118(12) 12 2×250 380 3.0 1.5 220 80
DD-12.0/60 12,000(10,300) 60 6 2 ¢500 2×6,000 167(17) 15 2×550 380 6.5 1.3 220 115
DD-15.9/80 15,900(13,700) 80 6 2 ¢500 2×6,000 167(17) 15 2×550 380 8.5 1.7 220 150
DD-20.0/100 20,00(17,200) 100 6 3 ¢500 3×6,000 167(17) 15 3×550 380 10.5 2.1 220 170
DD-24.0/120 24,000(20,650) 120 6 3 ¢500 3×6,000 167(17) 15 3×550 380 11.5 2.3 220 200
DD-28.0/140 28,000(24,100) 140 6 4 ¢500 4×6,000 167(17) 15 4×550 380 14.0 2.8 220 240
DD-32.1/160 32,100(27,600) 160 6 4 ¢500 4×6,000 167(17) 15 4×550 380 15.0 3.0 220 260
DD-37.4/200 37,400(32,200) 201 6 2 ¢600 2×10,000 200 18 2×1100 380 20.0 2.5 220 350
DD-46.8/250 46,800(40,300) 256 6 3 ¢600 3×10,000 200 18 3×1100 380 22.4 2.8 220 400
DD-56.2/310 56,200(48,300) 307 6 3 ¢600 3×10,000 200 18 3×1100 380 24 3.0 220 420

The DL-model air cooler is made for cold rooms with a storage temperature at about 0°C. This cold room stores fresh eggs, fruits, vegetables, tea, etc.

Technical Parameters of the DL-Model Air Cooler

Model
* Nominal Cooling Capacity
W(Kcal/h) t (storage temperature)=0℃
△t=t (storage temperature) -t0=7℃
Cooling Area
(m2)
Fan Distance
(mm)
Quantity Cooling Equipment Defrost Heater Weight
(kg)
Note
Diameter (D mm) Air Volume
(m3 /h)
Air Pressure
(Pa mmH2O)
Shot Range
(m)
Motor Power
(W)
Motor voltage
(V)
Fan Coil Power
(kW)
Water Coil power
(kW)
Voltage
(V)
DL-2.1/10 2,100(1,800) 10 4.5 1 ¢300 1700 98(10) 8 120 380 0.6 0.24 220 30 Applicable to
R134a
R404a
and
R507
DL-3.1/15 3,100(2,650) 15 4.5 2 ¢300 2×1700 98(10) 8 2×120 380 0.9 0.6 220 43
DL-4.2/20 4,200(3,600) 20 4.5 2 ¢300 2×1700 98(10) 8 2×120 380 0.9 0.6 220 50
DL-5.2/30 5,200(4,450) 30 4.5 3 ¢300 3×1700 98(10) 8 3×120 380 1.2 0.6 220 59
DL-8.2/40 8,200(7,050) 40 4.5 2 ¢400 2×3000 118(12) 12 2×250 380 2.0 1.0 220 75
DL-11.5/55 11,500(9,900) 55 4.5 2 ¢400 2×3000 118(12) 12 2×250 380 2.4 1.2 220 85
DL-16.7/80 16,700(14,350) 80 4.5 2 ¢500 2×6000 167(17) 15 2×550 380 3.0 1.5 220 110
DL-22.0/105 22,000(18,900) 105 4.5 2 ¢500 2×6000 167(17) 15 2×550 380 3.2 1.6 220 125
DL-25.8/135 25,800(22,200) 135 4.5 3 ¢500 3×6000 167(17) 15 3×550 380 3.8 1.9 220 165
DL-33.6/160 33600(28900) 160 4.5 3 ¢500 3×6000 167(17) 15 4×550 380 4.6 2.3 220 185
DL-38.7/185 38,700(33,300) 185 4.5 4 ¢500 4×6000 167(17) 15 4×550 380 5.4 2.7 220 220
DL-44.0/210 44,000(37,850) 210 4.5 4 ¢500 4×6000 167(17) 15 4×550 380 5.8 2.9 220 260
DL-52.9/260 52,900(45,500) 258.9 4.5 2 ¢600 2×10000 200 18 2×1,100 380 9.0 1.8 220 380
DL-67.2/330 67,200(57,800) 325.6 4.5 3 ¢600 3×10000 200 18 3×1,100 380 11.0 2.2 220 460
DL-83.4/410 83,400(71,700) 406.5 4.5 3 ¢600 3×10000 200 18 3×1,100 380 13.0 2.6 220 480
Technical Parameters of the DJ-Model Air Cooler

Model
* Nominal Cooling Capacity W(Kcal/h)
t(storage temperature)=-25℃
△t=t(storage temperature)-to=7℃
Cooling Area
(m2)
Fan Distance
(mm)
Cooling Equipment Defrost Heater Weight
(kg)
Note
Quantity Diameter (D mm) Air Volume
(m3 /h)
Air Pressure
(Pa mmH2O)
Shot Range
(m)
Motor Power
(W)
Motor voltage
(V)
Fan Coil Power
(kW)
Water Coil power
(kW)
Voltage
(V)
DJ-1.32/8 1,320(1,150) 8 9 2 ¢300 2×1,700 98(10) 8 2×120 380 1.8 0.9 220 35 Applicable to
R134a
R404a
and
R507
DJ-2.3/15 2,300(2,000) 15 9 3 ¢300 3×1,700 98(10) 8 3×120 380 2.4 1.2 220 50
DJ-4.0/20 4,000(3,450) 20 9 2 ¢400 2×3,000 118(12) 12 2×250 380 2.6 1.3 220 66
DJ-5.1/30 5,100(4,400) 30 9 2 ¢400 2×3,000 118(12) 12 2×250 380 3.0 1.5 220 72
DJ-7.8/40 7,800(6,700) 40 9 2 ¢500 2×6,000 167(17) 15 2×550 380 6.5 1.3 220 95
DJ-9.8/55 9,800(8,400) 55 9 2 ¢500 2×6,000 167(17) 15 2×550 380 8.5 1.7 220 105
DJ-12.8/70 12,800(11,000) 70 9 3 ¢500 3×6,000 167(17) 15 3×550 380 10.5 2.1 220 140
DJ-15.7/85 15,700(13,500) 85 9 3 ¢500 3×6,000 167(17) 15 3×550 380 11.5 2.3 220 158
DJ-18.8/100 18,800(16,160) 100 9 4 ¢500 4×6,000 167(17) 15 4×550 380 14.0 2.8 220 185
DJ-21.6/115 21,600(18,600) 115 9 4 ¢500 4×6,000 167(17) 15 4×550 380 15.0 3.0 220 220
DJ-23.9/140 23,900(20,600) 140 9 2 ¢600 2×10,000 420 20 2×1,500 380 20.0 2.5 220 330
DJ-29.0/170 29,000(24,900) 170 9 3 ¢600 3×10,000 420 20 3×1,500 380 22.4 2.8 220 360
DJ-35.9/210 35,900 (30,900) 210 9 3 ¢600 3×10,000 420 20 3×1,500 380 24.0 3.0 220 390

Advantages of the Air Cooler
1. Phosphorization and a secondary powder coating on this refrigeration equipment makes it easy to clean, beautiful and corrosion-resistant. Depending on customer preference, we make the shell of our air coolers from iron plates, galvanized plates, embossed aluminum plates, or stainless steel plates.
2. We offer two types of evaporators: θ12 and θ16. For each, the coils are arranged in such a way as to reduce side wind resistance and increase heat transfer efficiency.
3. This air-cooled equipment comes with a stable and quiet fan motor which has a large air volume. Different settings ensures the fan motor’s normal operation in moist environments or low temperatures. If required, we also offer explosion-proof motors.
4. All the connecting wires for our air cooler are placed in a junction box for easy installation and maintenance.
5. The grooved hanger on this refrigeration evaporator makes it easy to lift. We carry out a pressurized nitrogen treatment before delivery.
6. In order to defrost more efficiently, we install a U-shaped stainless steel electrical heating tube in the coil of the air cooler.
7. Our D-Series air coolers can be used together with different condensing units having a variety of refrigerating capacities.

Yanghu Refrigeration is not only a reliable building insulation material producer and cold room supplier offering structural insulated panels, cold room panels, cold room doors and custom cold rooms; but also a professional refrigeration equipment manufacturer providing high-quality and cost-effective air coolers used for cold rooms. If you are interested in our superior air coolers, contact us now for a great offer!

Related products
Send Message
Other Products
Inquiry
Inquiry