High Temperature Air Conditioning Unit
Features of High Temperature Air Conditioning Unit
1.This high temperature air conditioning unit provided by our company is a specially designed industrial cooling equipment;
2. As this Industrial air conditioner adopts the high-temperature refrigerant R142B, its outdoor unit could operate under a maximum ambient temperature of 80 ℃;
3. This automatic air conditioning unit adopts a mechanical controller;
4. According to working conditions, we could provide quality cabinet air conditioning equipment of this model which adopts the #304 stainless steel metal plates and cooper heat exchanger.
Front Return/Supply Type High Temperature Air Conditioning UnitTechnical Specifications of High Temperature Air Conditioning Unit
Indoor unit model Parameter Project | ||||||
Unit characteristic | Cooling capacity | kW | 7.3 | 14 | 30 | |
Input power | kW | 3.6 | 6.8 | 14.5 | ||
Air flow | m³/h | 1550 | 3000 | 6300 | ||
ESP | Pa | 0 | ||||
Indoor unit noise | dB(A) | ≤60 | ≤62 | ≤65 | ||
Liquid pipe size | inch | Φ1/2 | Φ1/2 | Φ5/8x2 | ||
Gas pipe size | inch | Φ1/2 | Φ1/2x2 | Φ3/4x2 | ||
Connecting pipe direction | Connecting on the left and right side | |||||
Power supply | 3P~50Hz~380V | |||||
Outdoor unit number | PC | 1 | 1 | 2 | ||
Outdoor unit | Outdoor unit model | |||||
Condenser | Type | Copper tube aluminum fin | ||||
Fin type | High efficiency corrugated aluminum fin | |||||
Fan | Type | Low noise centrifugal fan | ||||
Power | kW | 0.37 | 0.55 | 0.75x2 | ||
Unit dimension | Width | mm | 965 | 1085 | 1135 | |
Length | mm | 500 | 550 | 600 | ||
Height | mm | 848 | 973 | 1073 | ||
Outdoor unit noise | dB(A) | ≤63 | ≤65 | ≤67 | ||
Weight | kg | 80 | 95 | 115 | ||
Indoor unit | Compressor | Type | Hermetic scroll type | |||
number | 1 | 2 | 2 | |||
Power supply | 3P~50Hz~380V | |||||
Refrigerant | Type | R142b | ||||
Volume kg | 2.8 | 5.6 | 11.6 | |||
Evaporator | Type | Inner grooved copper tube aluminum fin | ||||
Fin type | aluminum fin in Louver shape | |||||
Throttle type | expansion valve | |||||
Fan | Type | Low noise centrifugal fan | ||||
Drive mode | Motor drive | |||||
Power | kW | 0.18 | 1.37 | 1.1 | ||
Air filter | Primary nylon filter | |||||
Unit dimension | Width | mm | 590 | 933 | 1470 | |
Length | mm | 480 | 520 | 600 | ||
Height | mm | 1820 | 1870 | 1920 | ||
Weight | kg | 150 | 265 | 395 |
Please note that
1. The maximum working temperature for its outdoor unit is 80 ℃;
2. There is no heat pump system in this high temperature air conditioning unit.