Low Voltage Power Factor Correction and Harmonic Filtering Equipment
- Low voltage power factor correction and harmonic filtering equipment
- Low voltage power factor correction and harmonic filtering equipment
- Reactive power compensation controller
Application
Low voltage power factor correction and harmonic filtering equipment is commonly applied to low voltage distribution systems, which is featured as low power factor, large harmonic current and unsteady load. This equipment can eliminate harmonics and improve power factor, which is widely applied to frequency conversion equipment, soft starter, uninterruptible power supply and other electrical equipment with large harmonic current and reactive load. The power factor correction and harmonic filtering equipment is commonly used in electric power, paper making, chemical industry, construction materials, textile industry and other fields.
Current grade | 125A~160A | 200A | 250A | 300A | 350A | 400A | 500A |
Compensation capacity | 100Kvar | 120Kvar | 150Kvar | 200Kvar | 240Kvar | 300Kvar | 400Kvar |
The main bus size | 30*3mm | 40*4mm | 60*6mm | ||||
AC input | |||||||
Rated voltage | 380V | ||||||
Rated frequency | 50 Hz (1±2%) | ||||||
Compensation way | Single phase, three phase three wire(3L), | ||||||
Specifications | |||||||
Target power factor | In the range of equipment output capacity, to achieve the set requirements | ||||||
Compensation way | reactive compensation | ||||||
Response time | < 20ms | ||||||
Overload protection | Automatic limit to rated current output | ||||||
Overall power consumption | < 3% | ||||||
Noisy | < 65dB(A) | ||||||
Environment condition | |||||||
Working temperature | -25℃~45℃ | ||||||
Storage temperature | -20℃~65℃ | ||||||
Relative humidity | < 90%(25℃) | ||||||
Work pattern | Automatic limit to rated current output | ||||||
Operation display | LED control panel; operation parameter setting; touch button operation; multi parameter display | ||||||
Display accuracy | Current±5%FS | ||||||
Expansion capability | Parallel connection of the same type | ||||||
Protection | Input under-voltage, lacking input phase, over-current, overheating, DC bus under voltage, overload automatic current limit protection | ||||||
Installation requirements | Installation point without violent vibration, no conductive and explosive dust, no corrosive gas, no more than 5 degrees slope angle. | ||||||
IP grade | Ip20(higher protection level can be customized) |
High | Width | Width |
2200mm | 600mm | 600mm 800mm 1000mm |
800mm | ||
1000mm |
Our low voltage power factor correction and harmonic filtering equipment can be customized based on the requirement of customers.
Major components
Cabinet body, generatrix, main loop switch, fuse switch, low voltage reactive power automatic compensation controller, Intelligent harmonic suppression reactive power compensation integrated module ( including of capacitor, thyristor, power magnetic force keeping relay, electric reactor, miniature circuit breaker), busbar, amperemeter, lightning arrester, capacitor indicator, etc.
Feature
1. Our equipment has two mode of operation, manual control or electric operation.
2. The compensator is installed on the ground and connection mode adopts fixed joint.
3. The surface of metal components is galvanized or treated with electrostatic epoxy powder, which has strong corrosion resistance.