Harmonic Filter Reactor
Request a Quote
Introduction
The harmonic filter reactor is used in series connection with filter capacitor banks to form resonant circuit for filtering specified higher harmonic currents.
Features
A. Our filter reactor provides decreased electrical loss and extended service life of equipment.
B. The filter choke is able to eliminate interference with other equipment
C. The filter reactor boasts surface protection from UV radiation and pollution.
D. Low Q-factor, maintenance-free design
E. Environmentally friendly
F. Conservative temperature rise
G. High mechanical strength
H. Tapping adjustable
I. Customized space-saving solutions for installations of the filter inductor in compact areas are available at Huashenglong.
Technical Parameters
No. | Rated Capacity | Model | System Voltage | Rated Current | Rated Inductance | Inductance Range | External Diameter | Height | Total Height | Assembly Height | Point | Single Phase Weight |
kvar | kV | A | mH | % | mm | mm | mm | mm | kg | |||
1 | 18 | LKGKLT-6-500-0.23 | 6 | 500 | 0.23 | ±5 | 1510 | 430 | 2150 | 1320 | 3 | 516 |
2 | 33 | LKGKLT-6-238-1.86 | 238 | 1.86 | ±5 | 1500 | 530 | 2255 | 1320 | 3 | 559 | |
3 | 55 | LKGKLT-6-300-1.95 | 300 | 1.95 | ±5 | 1570 | 575 | 2580 | 1380 | 4 | 752 | |
4 | 77 | LKGKLT-6-365-1.85 | 365 | 1.85 | ±5 | 1600 | 540 | 2430 | 1380 | 4 | 652 | |
5 | 125 | LKGKLT-6-400-2.48 | 400 | 2.48 | ±5 | 1710 | 585 | 2600 | 1550 | 4 | 894 | |
6 | 12 | LKGKLT-6.3-140-1.88 | 6.3 | 140 | 1.88 | ±5 | 1490 | 535 | 2395 | 1320 | 3 | 527 |
7 | 18 | LKGKLT-6.3-410-0.35 | 410 | 0.35 | ±5 | 1310 | 485 | 2180 | 1150 | 3 | 551 | |
8 | 27 | LKGKLT-6.3-405-0.52 | 405 | 0.52 | ±5 | 1360 | 540 | 2280 | 1150 | 4 | 631 | |
9 | 37 | LKGKLT-6.3-220-2.46 | 220 | 2.46 | ±5 | 1550 | 610 | 2565 | 1320 | 4 | 733 | |
10 | 5.9 | LKGKLT-10-102-1.82 | 10 | 102 | 1.82 | ±5 | 1160 | 470 | 2160 | 980 | 3 | 275 |
11 | 16 | LKGKLT-10-108-4.46 | 108 | 4.46 | ±5 | 1070 | 445 | 2045 | 920 | 3 | 278 | |
12 | 32 | LKGKLT-10-108-8.73 | 108 | 8.73 | ±5 | 1120 | 550 | 2320 | 950 | 3 | 342 | |
13 | 1642 | LKGKLT-12-622-13.52 | 12 | 622 | 13.52 | ±5 | 1750 | 700 | 2588 | 1580 | 4 | 1881 |
14 | 135 | LKGKLT-18.2-145-20.45 | 18.2 | 145 | 20.45 | ±5 | 1480 | 590 | 1950 | 1300 | 4 | 628 |
15 | 175 | LKGKLT-18.2-345-4.68 | 18.2 | 345 | 4.68 | ±5 | 1370 | 425 | 2125 | 1180 | 3 | 601 |
16 | 542 | LKGKLT-18.2-316-17.28 | 316 | 17.28 | ±5 | 1680 | 600 | 2615 | 1520 | 4 | 1059 | |
17 | 1725 | LKGKLT-18.2-414-32.06 | 414 | 32.06 | ±5 | 1790 | 785 | 2045 | 1580 | 4 | 1693 | |
18 | 100 | LKGKLT-35-102-30.62 | 35 | 102 | 30.62 | ±5 | 1390 | 490 | 2115 | 1220 | 3 | 542 |
19 | 156 | LKGKLT-35-102-47.81 | 102 | 47.81 | ±5 | 1490 | 580 | 2195 | 1320 | 4 | 625 | |
20 | 310 | LKGKLT-35-105-89.42 | 105 | 89.42 | ±5 | 1750 | 810 | 2505 | 1580 | 4 | 853 | |
21 | 350 | LKGKLT-35-105-101.0 | 105 | 101.06 | ±5 | 1970 | 630 | 2895 | 1800 | 4 | 1046 | |
22 | 914 | LKGKLT-35-100-291.12 | 100 | 291.12 | ±5 | 2060 | 845 | 3445 | 1850 | 4 | 1784 | |
23 | 1333 | LKGKLT-35-155-176.71 | 155 | 176.71 | ±5 | 2260 | 875 | 4275 | 2100 | 4 | 1995 |